|
AHU & Coil
Cleaning
By Don
Dorff, ASCS
Air Quality Controllers
For many duct cleaning
companies, there is the age-old question, “What is the best way to
effectively clean an air handling unit?” As an ASCS Technician
and owner of Air Quality Controllers, I found that there are no specific
guidelines for cleaning the interior components of AHU’s. Over
the last three years, I have developed a process that will restore the
coil pressure drop within 10% of the original pressure drop from when
the unit was first installed.
The first step to take
in completing this task is to take accurate measurements of the existing
pressure drop. I use a Magnehelic to take two measurements on the
unit before I start the cleaning process. The first would be to
measure the pressure drop on the upstream/return side of the coil.
Then, measure the pressure drop on the downstream/supply side of the
coil. Record your data so that a quantitative comparison can be
made when cleaning is complete. Now you can shut the unit off
using Lock Out/Tag Out procedures. Next, remove the filters and
mark the positions of the outside air and the return dampers.
Close these dampers. If there is a damper for the supply, mark it
and close it. If there is not a damper, use a bladder to protect
the supply ductwork.
Now you are ready to
start the actual cleaning. Always wear a respirator mask and
contact clean both sides of the coil to remove the larger debris and
accumulation. The upstream side will appear dirtier than the
downstream side. Be very careful not to apply too much pressure.
The coil fins can be bent and damaged very easily. Wearing a respirator
mask, eye protection and ear protection, blow out the coil from the
downstream side to the upstream side of the coil. Visually inspect
both sides of the coil by shining a light between the fins. The
technician should be looking for any remaining debris. If
necessary, air wash the coil a second time and inspect it.
In many cases, it is
just as difficult to gain access to the blower fan as it is to clean it.
Depending on the unit, the technician will have to remove panels, safety
grates and/or belt guards to accomplish this. Typically the
accumulation on a blower fan wheel and housing is “Caked
On,” I have found that a wire brush and a scraper are adequate for
loosening the accumulation. While brushing and scraping, have a
vacuum hose in hand to remove the loosened debris. This will help
the technician see if he/she has overlooked any areas that still need to
be cleaned. All panels, safety grates, and/or belt guards should be
cleaned before they are installed.
Once the coil has been
air washed and the blower fan is clean, the technician can start
cleaning the rest of the AHU. This would include the interior
walls, filter racks, and the floor. I have found that the most
efficient way of doing this is to start at the top/ceiling and work
downward to the bottom/floor.
If the unit has a
drain pan, I recommend that the technician applies a coil cleaner. This
will dissolve stubborn calcium deposits that may be remaining on the
coil. It is important to rinse the coil thoroughly with water to
remove chemical residues. During the rinse process, make sure the
drain is operating properly. If there is not a drain pan, DO NOT
perform this last step.
With the cleaning
portion of the process completed, the technician must set the dampers to
their original position, remove bladders, install new filters and
replace panels. Next, remove the Lock Out/Tag Out, turn the unit
on and test the unit. Record the results and include them in the
Post Project Report.
Depending on the size
of the AHU, a thorough cleaning can take anywhere from 3 hours to 1.5
days. With this in mind, make sure the client is aware that the
AHU could possibly shut down for 24 hours or more. This process
has proven to be successful for our organization and it provides
excellent results for out clients.
BACK
|